If you generate hazardous waste, EPA’s RCRA rules require spill control equipment where the waste is made and stored, plus regular inspections for leaks. Permitted storage facilities also have a specific containment formula, which many generators use as their benchmark.
The short version
- Small and large quantity generators must equip areas where hazardous waste is generated or accumulated with spill control equipment, unless the waste’s hazards don’t call for it, and keep it tested and maintained (40 CFR 262.16(b)(8), 40 CFR 262.252).
- Generators must inspect central accumulation areas at least weekly for leaking or deteriorating containers.
- Permitted storage facilities need containment that holds 10% of the total volume or 100% of the largest container, whichever is greater (40 CFR 264.175).
- Federal generator rules don’t set a containment capacity for container areas, but state rules, fire codes and permits often do, and the 264.175 formula is the usual benchmark.
Generators: spill equipment and inspections
Your rules depend on your generator category (very small, small or large quantity generator). For small and large quantity generators:
- Required equipment. All areas where hazardous waste is generated or accumulated must have an alarm or communication system, a phone or radio to call for help, fire extinguishers, spill control equipment and decontamination equipment, and water or foam for fire control. The exception is equipment that none of the hazards at your site could require, or that isn’t safe in a particular area. Small quantity generators: 40 CFR 262.16(b)(8)(ii). Large quantity generators: 40 CFR 262.252.
- Keep it ready. Spill control equipment must be tested and maintained so it works in an emergency (40 CFR 262.253 for large quantity generators; 262.16(b)(8)(iii) for small).
- Weekly inspections. Inspect central accumulation areas at least weekly, looking for leaking containers and corrosion or other deterioration (40 CFR 262.16(b)(2)(iv); 40 CFR 262.17(a)(1)(v)).
- Keep containers closed and compatible. Containers must be in good condition, compatible with the waste, kept closed except when adding or removing waste, and handled so they won’t rupture or leak.
Large quantity generators storing waste in tanks must also meet the secondary containment rules for tank systems in 40 CFR 265.193.
The 10% or largest-container formula
For permitted treatment, storage and disposal facilities, 40 CFR 264.175 requires a containment system for container storage areas:
- A base under the containers that is free of cracks or gaps and impervious enough to hold leaks, spills and rainwater until they are removed.
- A sloped base or other way to drain liquids, unless the containers are elevated or otherwise kept out of standing liquid.
- Capacity for 10% of the total volume of the containers or the volume of the largest container, whichever is greater. Containers with no free liquids don’t count toward the total.
- Run-on kept out, unless there is extra capacity for it.
- Spilled waste and rainwater removed from the sump or collection area quickly enough to prevent overflow.
Even where this section doesn’t apply to you directly, it is a common benchmark for sizing containment for drum and tote storage, and some state rules and fire codes use the same approach.
Sizing examples
Outdoor containment also needs room for rain. The Berm Sizing Calculator has a hazardous waste mode that applies this formula.
Spills during transport
A transporter who has a hazardous waste discharge must take appropriate immediate action to protect health and the environment, such as notifying local authorities and diking the discharge area (40 CFR 263.30), and must clean up the discharge (40 CFR 263.31). Vehicle spill kits with socks and pillows are the usual way to dike a spill on the road.
Products that help
Hazardous waste storage checklist
- Confirm your generator category; it decides which rules apply.
- Keep a spill kit matched to your waste (hazmat for acids, bases and solvents) in every generation and accumulation area.
- Check spill equipment during your weekly inspection and restock what is used.
- Keep containers closed, labeled, in good condition and on containment.
- Size containment with the 10% or largest-container formula, plus rain if outdoors.
- Check your state rules and local fire code, which may require more.
Sources
Not sure what fits your site? Call (800) 869-9633, Mon–Fri 9–5 PT, or email [email protected]. Tell us what you store and where, and we’ll help you size it.
Last reviewed November 2026 against the current Code of Federal Regulations (eCFR). This is a plain-English summary, not legal advice. State rules, local fire codes and your own plan or permit can be stricter, so check the regulation text and your permit before you rely on it.