If your facility keeps oil in drums, totes or tanks, EPA’s Spill Prevention, Control, and Countermeasure (SPCC) rule may require a written plan and secondary containment. Here is what the rule says, in plain English, and how to size containment for it.

The short version

  • SPCC applies when you store more than 1,320 gallons of oil above ground (counting only containers of 55 gallons or more) or more than 42,000 gallons completely buried, and a spill could reasonably reach navigable waters or their shorelines.
  • “Oil” is broad: fuel, lube and hydraulic oil, used oil, and also vegetable oils, animal fats and synthetic oils.
  • Bulk storage containers and portable containers such as drums and totes need secondary containment for the entire capacity of the largest single container, plus room for rain if they sit outside.
  • You need a written SPCC Plan. Most facilities need a Professional Engineer to certify it; “qualified facilities” with 10,000 gallons or less can self-certify.
  • Train oil-handling staff, and hold a discharge prevention briefing at least once a year.

Does the SPCC rule apply to you?

Under 40 CFR 112.1, the rule covers a facility when all three of these are true:

  1. You handle oil at a fixed site. The rule covers non-transportation-related facilities that store, use, process, transfer or distribute oil. That includes repair shops, fleet yards, manufacturers, farms, construction sites and utilities.
  2. You are over a storage threshold. Aggregate aboveground capacity over 1,320 U.S. gallons, or completely buried capacity over 42,000 gallons. Only containers of 55 gallons or more count. Permanently closed containers and “motive power” containers, such as a vehicle’s own fuel tank, are left out.
  3. A spill could reach water. Because of your location, a discharge could reasonably be expected to reach navigable waters of the U.S. or adjoining shorelines. EPA says you must judge this on geography alone (distance to water, slope, drainage) and not count your dikes, berms or other man-made barriers.
Counting example. Four 55-gallon drums of hydraulic oil (220 gal) + one 1,000-gallon diesel tank + two 275-gallon totes of used oil (550 gal) = 1,770 gallons, which is over the 1,320-gallon threshold. A 5-gallon pail of oil does not count; a 55-gallon drum does, even when it is half full, because the rule counts capacity.

The rule defines oil in 40 CFR 112.2 as “oil of any kind or in any form,” including petroleum, fuel oil, synthetic oils, mineral oils, vegetable oils and animal fats.

What secondary containment the rule requires

The general requirement

40 CFR 112.7(c) requires “appropriate containment and/or diversionary structures or equipment” to keep a discharge from reaching water. The whole system, walls and floor included, has to be able to hold oil until it is cleaned up. The rule lists acceptable methods for onshore facilities:

  • Dikes, berms or retaining walls
  • Curbing or drip pans
  • Sumps and collection systems
  • Culverts, gutters or other drainage systems
  • Weirs, booms or other barriers
  • Spill diversion ponds
  • Retention ponds
  • Sorbent materials

Containment can be passive (a berm or spill pallet that is always in place) or active (spill kits, sorbents or drain covers your crew deploys when something spills). Active measures only work if they are close by and people know how to use them before the oil escapes.

Bulk storage containers and drums: sized containment

For tanks and other bulk storage containers, 40 CFR 112.8(c)(2) requires “a secondary means of containment for the entire capacity of the largest single container and sufficient freeboard to contain precipitation.” Diked areas must be impervious enough to hold the oil.

The same sizing applies to mobile or portable containers such as drums, totes and portable tanks under 112.8(c)(11): containment for the largest single container or compartment, with freeboard for rain. (Mobile refuelers and other non-transportation tank trucks follow the general requirement instead.)

Keeping containment working

  • Remove oil promptly. Fix visible leaks and promptly remove any oil that collects inside diked areas (112.8(c)(10)).
  • Check rainwater before you drain it. Keep drain valves sealed closed, inspect the water for an oil sheen before releasing it, and record each drainage event (112.8(c)(3)).

How to size it

Start with the largest single container that will sit in the containment, not the total of everything inside. Then add freeboard for rain if the containment is outdoors.

The rule does not name a percentage. A common rule of thumb is 110% of the largest container. Many engineers instead size outdoor containment for a design storm named in the plan, often the 25-year, 24-hour rainfall for the site.

Example. A 1,000-gallon diesel tank stored outdoors needs containment for at least 1,000 gallons plus rain, so about 1,100 gallons by the 110% rule of thumb. A berm holding eight drums needs to hold one drum (55 gallons) plus rain, not all eight.

Open the Berm Sizing Calculator

Your SPCC Plan, inspections and training

  • Certification. A licensed Professional Engineer must review and certify the plan (40 CFR 112.3(d)), unless you are a qualified facility.
  • Qualified facilities can self-certify (40 CFR 112.6). You qualify with 10,000 gallons or less of aggregate aboveground oil storage and no single discharge over 1,000 gallons, or two discharges over 42 gallons each within any 12 months, in the past three years. Tier I facilities (no single container over 5,000 gallons) can use EPA’s plan template.
  • Response equipment goes in the plan. The plan describes your countermeasures for discovering, responding to and cleaning up a discharge (112.7(a)(3)(iv)). That is where your spill kits, sorbents and drain covers belong.
  • Inspections and records. Inspect and test per your plan, and keep signed records with the plan for three years (112.7(e)).
  • Training. Train oil-handling personnel on equipment, discharge procedures, pollution rules and the contents of the plan; name one person accountable for discharge prevention; and hold briefings at least once a year (112.7(f)).

Products that help

SPCC containment checklist

  • List every oil container of 55 gallons or more and add up the capacity.
  • Map where a spill would flow: floor drains, storm drains, ditches and slopes.
  • Give each tank, tote and drum containment sized for its largest container, plus rain if it is outdoors.
  • Put spill kits and drain covers where oil is transferred, and make sure people know where they are.
  • Inspect containment, remove oil promptly, and drain rainwater only after checking it.
  • Train oil handlers, brief them at least once a year, and keep records for three years.